Product Selection

Rating (kVA) Type ID No. PO (W) Pk (W) Uk % Sound pressure dB(A) Tot. weight (kg) Oil weight (kg) Length (mm) Width (mm) Height (mm) Loss  start request
1000 DOTE 1000/10 1723 1700 10500 6.00 49 2800 580 1930 2140 1930 Low Loss
1250 DOTE 1250/10 1022 2000 13500 6.00 52 3450 700 2010 2140 2040 Standard Loss
1500 DOTE 1500/10 1018 2200 17000 6.00 52 3900 860 2010 2140 2120 Low Loss
1500 DOTE 1500/10 1136 1200 1400 5.5 52 4200 900 2200 1900 1900 Low Loss
1600 DOTE 1600/10 1021 2200 17000 6.00 52 4200 870 2060 2190 2130 Standard Loss
2500 DOTE 2500/10 1020 3200 26500 6.00 57 6300 1380 2320 2470 2590 Standard Loss
3000 DOTE 3000/10 1115 3200 26500 6.00 57 6500 1500 2400 2350 2600 Low Loss
50 DOTE 50/10 1070 140 880 4.00 43 570 140 900 680 1100 Low Loss
100 DOTW 100/10 1011 300 1500 4.75 43 660 150 945 620 1185 Standard Loss
1000 DOTW 1000/10 2010 1400 7000 4.75 49 3070 620 1730 910 1675 Standard Loss
1000 DOTW 1000/10 1135 925 9000 4.75 49 3150 650 2000 1900 1750 Standard Loss
2000 DOTW 2000/10 1061 2000 20000 6.00 53 5120 990 1980 2120 2370 Low Loss
300 DOTW 300/10 1132 360 3900 4.75 46 1350 260 1300 1600 1400 Low Loss
300 DOTW 315/10 2007 600 2800 4.75 46 1290 260 1190 760 1261 Low Loss
500 DOTW 500/10 2008 1000 4100 4.75 47 1700 330 1500 770 1410 Standard Loss
500 DOTW 500/10 1133 510 5500 4.75 47 1900 350 1700 1650 1550 Standard Loss
750 DOTW 800/10 1007 1200 6000 4.75 48 2450 540 1690 925 1620 Low Loss
800 DOTW 800/100 1134 780 7700 4.75 48 2550 550 1900 1750 1650 Low Loss

Special equipment

Components and systems for neutral-point connection

Medium-voltage systems in Europe are largely operated as resonant-earthed systems. SGB offers a complete range of products for the necessary neutral-point connection:

  • Arc suppression coils
  • Fixed coils, off-circuit variable tapped coils as well as coils variable under load. The variable coils can be operated with the fitted electronic regulators and have an automatic mode.
  • Neutral electromagnetic couplers
  • Earthing transformers
  • Earth fault combinations consisting of neutral electromagnetic couplers and arc suppression coils.

 
In special cases the use of oil-immersed equipment is restricted due to environmental protection considerations. In these cases we use special synthetic or organic esters (e.g. Midel 7131).

Selection accessories

Monitoring devices

  • dial-type thermometer
  • temperature alarm device
  • magnetic oil-level indicator
  • pressure relief valve
  • Buchholz relay protection
  • hermetic protection block
  • dehydrating breather

Current transformers / thermal images can also be mounted on request.

Design variations

  • tap changer
  • outer and inner cone bushings
  • transformer terminals and covers
  • cable boxes
  • terminal boxes

Insulation liquids

  • mineral oil acc to DIN VDE 0370 Part 1
  • synthetic or organic ester (Midel 7131) acc to DIN VDE 0375 Part 1 resp. DIN EN 61099 (IEC 1099)