DTTH1N 800/20

  • Capacity (kVA): 800
  • Primary voltage: 20
  • Um1 (kV): 24
  • Secondary voltage (kV): 0,4

  • Um2 (kV): 1,1
  • Connection group: Dyn5/11
  • PO (W): 1300
  • Pk 120 °C (W): 8000

  • uk %: 6
  • Lp(A) (0,3m)dB:
  • Lw (A) dB: 64
  • Total weight (kg): 2650

  • Total length (mm) A: 1671
  • Total width Transformer (mm) C: 820
  • Total height (mm) B: 2000
  • Centre distance of rollers (mm) K: 670

  • Total width of undercarriage (mm): 820
  • Diameter of rollers (mm) M: 125
  • Width of rollers (mm): 40
Execution acc. to DIN 42 523 – Edition Dec. 93 HD 464.S2 Indoor installation E2; C2; F1 With tappings ±5 % connection group up to SN 100 kVA Yzn5 from SN > 100 kVA Dyn5
  • 11 HV-terminal
  • 12 LV-terminal,acc. to DIN 46206, Part 2
  • 13 Earth connection DIN 48088-B-M12
  • 14 Terminal strip for temperature control
  • 21 Rating plate
  • 22 Terminal marking plates acc. to DIN 42402
  • 23 Warning plate VS 2 acc. to DIN 40008, Part 2
  • 31 Roller form H acc. to DIN 42562, Part 1 (actually draft) for bidirectional movement
  • 32 Lifting lugs
  • 33 Hauling lugs for bi-directional shifting of the transformer
  • 34 Fixing lugs for transport
Back to overview