DTTH1N 1600/10

Capacity (kVA): 1600Primary voltage (kV): 10Um1 (kV): 12Secondary voltage (kV): 0,4
Um2 (kV): 1,1Connection group: Dyn5/11PO (W): 2200Pk 120 °C (W): 13000
uk %: 6Lp (A) (dB): Lw (A) (dB): 68Total weight(kg): 4250
Total length (mm) A: 1870Total width Transformer (mm) C: 980Total height (mm) B: 2250Distance core centre LV bars (mm) D:
Distance core centre HV voltage bars (mm) E: Centre distance of rollers (mm) K: 820Total width of undercarriage (mm): 980Diameter of rollers (mm) M: 160
Width of rollers (mm): 50
Execution acc. to DIN 42 523 – Edition Dec. 93 HD 464.S2 Indoor installation E2; C2; F1 With tappings ±5 % connection group up to SN 100 kVA Yzn5 from SN > 100 kVA Dyn5
  • 11 HV-terminal
  • 12 LV-terminal,acc. to DIN 46206, Part 2
  • 13 Earth connection DIN 48088-B-M12
  • 14 Terminal strip for temperature control
  • 21 Rating plate
  • 22 Terminal marking plates acc. to DIN 42402
  • 23 Warning plate VS 2 acc. to DIN 40008, Part 2
  • 31 Roller form H acc. to DIN 42562, Part 1 (actually draft) for bidirectional movement
  • 32 Lifting lugs
  • 33 Hauling lugs for bi-directional shifting of the transformer
  • 34 Fixing lugs for transport


This website uses cookies

This website needs certain cookies to work correctly. These cookies are technically necessary. If you allow us, we will also use statistic cookies to help gather statistics about your visits to this site in order to improve our service. I agree and I am aware that I can change my choices at any time on the privacy policy page.