DOTUL

Capacity (kVA): 630Loss-combination: A0BkPO (Watt): 600PK (Watt): 5400
uk (%): 4Lp(A) (0,3m)dB: 38Lw (A) dB: 47Length (mm): 1230
Width (mm): 830Height (mm): 1450Total weight (kg): 1790Oil (kg): 360
Winding material (kg): 275Core material (E Steel): GOMass of corematerial (kg): 795
Execution acc. to DIN EN 50588 (HD 428.1 S1) Hermetic design, for outdoor installation with HV porcelain bushings Max. ambient temperature 40 ºC, max. installation height 1000 m above sea level Routine test acc to DIN EN 60076-1 max. system voltage HV: 24 kV / max. system voltage LV: 1,1 kV Deviating parameters resp deviating design (e.g. conservator design) on request deliverable with deviating dimensions and masses.
  • 11 HV bushings acc. to DIN 42531 in accordance with the series voltage DIN 43675
  • 12 LV bushings acc. to DIN 42530 with flat terminal acc to
  • 13 Earth connection BM 12 DIN 48088
  • 21 Rating plate
  • 22 Terminal marking plates
  • 31 Bidirectional rollers DIN 42561
  • 32 Lifting lugs also for active part including cover
  • 33 Hauling lugs also for bi-directional shifting of the transformer
  • 34 Hauling lugs
  • 41 Oil drain device DIN 42551
  • 42 Filling tube with female thread G 1½ A
  • 61 Thermometer pocket T DIN 42554
  • 91 Off-circuit tap changer for setting HV tappings


This website uses cookies

This website needs certain cookies to work correctly. These cookies are technically necessary. If you allow us, we will also use statistic cookies to help gather statistics about your visits to this site in order to improve our service. I agree and I am aware that I can change my choices at any time on the privacy policy page.