SGB-SMIT Group is able to deliver Cast Resin Transformers (from production sites in Germany, Malaysia and the USA) with capacities up to 25 MVA and series voltages up to
36 kV. Our offer includes converter transformers, distribution transformers and special transformers. With more than 30 years experience in the construction of cast resin transformers, SGB-SMIT Group has worldwide expertise, and this is expressed in remarkably high quality coefficients such as mean time between failures (MTBF) of over
2,400 years.
Type | Three Phase Cast Resin Transformer |
Material of HV winding | Aluminium/copper |
Material of LV winding | Aluminium/copper |
Cooling | AN |
Frequency | 50 Hz |
Phases | 3 |
Max. installation height | < 1000 m above sea level |
Highest voltage of equipment Um HV | 7,2 kV 12 kV 17,5 kV 24 kV 36 kV |
Power frequency withstand voltage | 20 kV 28 kV 38 kV 50 kV 70 kV |
Impulse withstand voltage (peak) | 40 or 60 kV 60 or 75 kV 75 or 95 kV 95 or 125 kV 145 or 170 kV |
Highest voltage of equipment Um LV | 1,1 kV |
Power frequency withstand voltage | 3 kV |
Environmental, climate and fire class | E1 on request E2; C2; F1 |
Max. ambient temperature | 20°C yearly average / 30°C daily average / 40°C max. ambient temperature |
Winding temperature rise | 100 K |
Connection group | Dyn 5 |
Tappings (HV side) | ± 2 x 2,5%, ± 5% |
Insulation class | F |
Requirements / standards | VDE 0532 Part 6, IEC 726 |
Tests | Acc to VDE0532 Part 6, Acc to IEC 726 |
Equipment and accessories | 2 PTC sensors per phase for alarm and trip, lifting lugs, earthing terminal, rating plate , carriage with rollers for bi-directional movement, tappings reconnectable by links, coating of core and clamping bar: RAL5013 |
For specifying cores for cast resin transformers, no-load losses, noise and no-load current are essential quality features which are, in many cases, of decisive importance. Thus, the core design is an important engineering task. This includes the precise geometrical design, determination of the material properties of the magnetic sheet to be used and many details, including design measures such as those to control vibrations, slanting positions and other mechanical requirements.
Today, transformer cores are produced on special machines which manufacture complete cores in accordance with our specifications out of prefabricated and precisely pre-measured sheet coils. To this effect, SGB-SMIT deploys top-quality specialists and cooperates with these experts very closely in long-term partnerships. Our logistics concept means that material is supplied daily on a just-in-time basis.
Core lamination with high-temperature resistant varnish is suitable for all – even extreme – installation conditions. This provides not only corrosion protection, but also enhances the core‘s stability, as the SGB-SMIT varnish penetrates between the individual laminations, bonding them to one another.
The core is fastened by a holding frame which consists of upper and lower steel clamps and flat tie bars resting directly against the core. The tie bars consist of non-magnetic flat steel and connect the lower and upper steel clamps via forces. The holding frame is designed so that the laminations are largely kept free of traction and pressure strain, as this is the only way to ensure that they retain their excellent loss- and noise-related properties. The lower yoke rests, supported by moulded parts of glass-fibre reinforced plastic, on the lower chassis beams to which bi-directionally adjustable rollers can be fastened. Depending on the requirements at the site of installation, various fastenings can be selected such as additional foot bridges, skids, vibration-reducing elements etc.


The high voltage winding (HV winding) is the heart of the cast resin transformer. It embodies the enormous technical know-how of SGB-SMIT.
Cast resin transformers are characterized by the conductors of the HV winding being embedded completely in an enclosed cast resin body with a smooth surface. Even if not specified so explicitly by the standard, this can be achieved in production of high voltage applications only using vacuum-encapsulated moulds. To this effect, the SGB-SMIT production technology and the materials used feature important USPs (USP = unique selling proposition) which distinguish them on the one hand from other cast resin transformers in terms of technology and, on the other hand, make them a highly reliable and extremely safe solution.
For our customers, these special features imply a high degree of safety both regarding operation and security regarding their investment decision.
R|eserves-equipped
Thermal reserves allow for overload
In this regard, SGB-SMIT cast resin transformers are not only one step ahead of oil transformers, but also of cast resin transformers made according to conventional technology. These use a continuously wound coil whose conductor consists of an aluminium coil and the winding/layer insulation of foil. The insulation corresponds only to insulation class F and even this qualification is only reached in conjunction with the entire insulation system - without thermal reserves.
This is completely different in the case of SGB-SMIT cast resin transformers, as SGB-SMIT uses forthe double-layer winding insulated profile wires whose primary insulation consists either of highlyheat-resistant polyesterimide varnish with a temperature index of 200°C or a Nomex thread covering of temperature class C (220°C). As SGB-SMIT cast resin transformers are utilized, due to their design, mainly according to temperature class F (155°C), primary insulation features considerable temperature reserves.

E|ndurance-enhanced
Ensuring a long service life
Cast resin transformers must dissipate the thermal loss produced in the windings to the cooling air via the coil surfaces. The coils are dimensioned so that the over temperatures admissible due to the
insulation class are not exceeded.
Cooling of conventional technology cast resin transformers with continuously wound coil is only possible via the two inside and outside surfaces of the cylindrical coil. To provide the required surface, the coils must be larger than required by the electrical parameters in many cases. The double-layer winding technology chosen by SGB-SMIT, on the other hand, permits straightforward introduction of additional cooling ducts within the coil. Thus, the cooling surface is gained and the design of the coils is ideal in view of their mechanical dimensions.
SGB-SMIT cast resin coils can even feature multiple cooling ducts.
SGB-SMIT cast resin transformers ensure a uniform temperature distribution within the coil in line with a reasonable material utilization. The optimized coil permits temperature reduction for the HV winding and additionally a uniform temperature distribution for the entire transformer.
S|urge-proof
Reliable handling of high surge voltages
Only SGB-SMIT cast resin transformers feature vacuum-encapsulated high voltage coils whose winding is designed as a double-layer winding. This means safety in the handling of surge voltages as are caused by lightning strikes or by vacuum circuit-breakers.
• The continuous coil winding of other transformers results in a strongly fluctuating voltage stress, especially of the input windings, as 70% of the surge voltage stress is taken
up by the first 30% of the windings. Thus, the risk of short-circuited coils increases considerably for these winding types.
• On the contrary, the SGB-SMIT double-layer winding ensures a linear surge voltage stress for all windings.


Q|uantum-leap
Reliably resistant to temperature shocks
During transport, cast resin transformers are subject to mechanical and – especially during operation – strong thermal shock stress. Thus, the transformer‘s capability of handling steep or extreme temperature increases safely is paramount. This feature depends decisively on the design of the cast resin composite material, the matrix, into which the conductors are encapsulated.
For the usual cast resin transformers, this composite material consists of an epoxy resin which is mixed by over 70% with a mineral based filler, primarily quartz powder. Such composite material can only reach the tensile strength of the epoxy resin, i. e. approx. 50 N/mm.
Quite the opposite is the case with SGB-SMIT. Here, the composite system consists of a glass-fibre reinforced epoxy resin between the layers and on the surface, with a high tensile strength in the range of 120 N/mm. The advantage of the composite system chosen by SGB-SMIT has proved its worth in various tests. The thermal shock tests according to IEC 60076-11, which are required for climate classification C2, based on a temperature of -25°C, were passed successfully by SGB-SMIT cast resin coils even at an initial temperature of -50°C.
The low voltage winding of SGB-SMIT cast resin transformers are almost always designed as foil winding.
The benefits of this form of winding are self-explanatory:


Exceptions exist, for technical reasons, only in case of minor ratings below 250 kVA and for higher system
voltages (> 3.6 kV).
For more than 40 years SGB-SMIT has been producing foil windings for distribution transformers and cast resin
transformers.
This long expertise ensures quality features.
Cast resin transformers can be equipped with fans for power increase. Through forced cooling a power increase of up to 40% is possible. With optimum interpretation, a greater value can also be reached. This is then determined by means of appropriate cooling in the test room.
The following variants are offered for the forced cooling of cast resin transformers:
If the solutions shown do not meet your demands, we would be only to pleased to compile customer-specific solutions for you. Please get in touch with us.
Please also look at the following information:
Temperature monitoring via PTC (resistors whose resistance changes quickly once the operating temperature is reached) is provided in general for each cast resin transformer. As the LV and HV windings are thermally balanced, the thermistors are located on the LV winding for reasons of insulation. They offer special protection of the vacuum-encapsulated high voltage windings against inadmissibly high temperatures which may occur in situations of overload, insufficient cooling and high ambient temperatures. Subject to customer‘s request, PT100 and core monitoring by PT100 or PTC are also possible. Non-contact temperature monitoring is also available.
As a rule, two systems are installed:

The following tripping units are available optionally for monitoring SGB Cast Resin Transformers:
We obtain heat detectors from ZIEHL with the following technical information:
PT100 heat detector Type TF101
Resistor heat detector Type MINIKA
For details of the marshalling panels please remove the following designs:


Transformers are capital goods with a service life of many decades; thus, the purchaser should not only focus on the comparison of acquisition prices, but also and especially of the presumable maintenance costs and those resulting from no-load losses (iron core) and load losses (windings).
SGB-SMIT offers different loss variants from normal to highly reduced values.
Higher acquisition costs due to higher outlay for laminations and winding materials coincide with lower operating costs.
It is relatively straightforward to evaluate idle losses, as these are incurred at a constant level over the entire service life of 8,760 hours/year. Evaluation of the load losses which exhibit quadratic growth or decline according to the load is slightly more difficult.
The use of transformers with reduced no-load losses is also profitable as it helps reduce noise emission.
To find the most cost-efficient interpretation of the actual case of application, it is important to know, which total costs are calculated with definite losses. The price can then be set compared to the cost price. Higher cost prices (as a result of higher expenditure for laminations and winding materials) are opposed to lower running costs. Thereby the average service life is fixed at 20 years.
Rating the no-load losses is relatively easy to carry out, as these occur consistently during the total operating time of 8760 hours a year. Using transformers with reduced no-load losses also pays off because there is a decrease in noise emission associated with that.
Rating the load losses is more difficult, as there can be a quadratic fall or rise with the strain.
Both the following tables contain sample calculations with different realistic expectations.
This shows that it pays to use SGB dry-type transformers with reduced losses.
Type DTTH with standard loss and type DTTHL with reduced no-load losses:
Average capacity % | 40 | 1) |
|
( 8760 h / per year ) |
|
|
|
| |||
Euros per KW/h : | 0,15 | 2) |
|
| |||
Type of transformer: | DTTH 1600/10 | DTTHL 1600/10 |
|
| High losses | Low losses | Saving |
No-load losses (Po) KW | 2,80 | 2,10 |
|
Short circuit losses (Pk 75°C )KW | 12,50 | 12,50 |
|
| |||
Losses KW/h per year Po | 24.528 | 18.396 | 6.132 |
Losses KW/h per year Pk (120°C) | 20.148 | 20.148 | 0 |
Total losses KW per year | 44.676 | 38.544 | 6.132 |
| |||
Cost per year Po , Euros | 3.679,20 | 2.759,40 | 920 |
Cost per year Pk , Euros | 3.022,20 | 3.022,20 | 0 |
Total cost Euros (per year) : | 6.701,40 | 5.781,60 | 920 |
| |||
Total losses |
|
|
|
After 1 year in Euros : | 6.701,40 | 5.781,60 | 920 |
After 3 years in Euros : | 20.104,20 | 17.344,80 | 2.759 |
After 5 years in Euros : | 33.507,00 | 28.908,00 | 4.599 |
After 10 years in Euros : | 67.014,00 | 57.816,00 | 9.198 |
After 20 years in Euros : | 134.028,00 | 115.632,00 | 18.396 |
Cost price Euros : | 26.985,00 | 28.507,00 | -1.522,00 |
| |||
Total cost after (1 year ) Euros : | 33.686,40 | 34.288,60 | -602,20 |
Total cost after (3 years ) Euros : | 47.089,20 | 45.851,80 | 1.237,40 |
Total cost after (5 years ) Euros: | 60.492,00 | 57.415,00 | 3.077,00 |
Total cost after (10 years ) Euros : | 93.999,00 | 86.323,00 | 7.676,00 |
Total cost after (20 years ) Euros : | 161.013,00 | 144.139,00 | 16.874,00 |
| |||
Price increase and inflation not included | |||
| |||
1) Strain with single-shift work ca.40% | |||
1) Strain with multi-shift work ca.70% | |||
| |||
2) Costs from your electric bill | |||
Type DTTH with standard losses and type DTTHIL with reduced no-load and short circuit losses:
Average capacity % | 70 | 1) |
|
( 8760 h / per year ) |
|
|
|
| |||
Euros per KW/h : | 0,15 | 2) |
|
| |||
Type of transformer: | DTTH 1600/10 | DTTHIL 1600/10 |
|
| High losses | Low losses | Saving |
No-load losses (Po) KW | 2,80 | 2,25 |
|
Short circuit losses (Pk 75°C )KW | 12,50 | 8,70 |
|
| |||
Losses KW/h per year Po | 24.528 | 19.710 | 4.818 |
Losses KW/h per year Pk (120°C) | 61.703 | 42.945 | 18.758 |
Total losses KW per year | 86.231 | 62.655 | 23.576 |
| |||
Cost per year Po , Euros | 3.679,20 | 2.956,50 | 723 |
Cost per year Pk , Euros | 9.255,49 | 6.441,82 | 2.814 |
Total cost Euros (per year) : | 12.934,69 | 9.398,32 | 3.536 |
| |||
Total losses |
|
|
|
After 1 year in Euros : | 12.934,69 | 9.398,32 | 3.536 |
After 3 years in Euros : | 38.804,06 | 28.194,96 | 10.609 |
After 5 years in Euros : | 64.673,44 | 46.991,60 | 17.682 |
After 10 years in Euros : | 129.346,88 | 93.983,19 | 35.364 |
After 20 years in Euros : | 258.693,75 | 187.966,39 | 70.727 |
Cost price Euros : | 26.985,00 | 33.600,00 | -6.615,00 |
| |||
Total cost after (1 year ) Euros : | 39.919,69 | 42.998,32 | -3.078,63 |
Total cost after (3 years ) Euros : | 65.789,06 | 61.794,96 | 3.994,10 |
Total cost after (5 years ) Euros : | 91.658,44 | 80.591,60 | 11.066,84 |
Total cost after (10 years ) Euros : | 156.331,88 | 127.583,19 | 28.748,68 |
Total cost after (20 years ) Euros : | 285.678,75 | 221.566,39 | 64.112,36 |
| |||
Price increase and inflation not included | |||
| |||
1) Strain with single-shift work ca.40% | |||
1) Strain with multi-shift work ca.70% | |||
| |||
2) Costs from your electric bill | |||
The sample calculations show that own consumption for the operator of the transformers is more important than the cost price.

The following parts can possibly be used as options:
Earthing switch
As standard we offer earthing switches from the company Driescher.
If you prefer other makes, we can naturally also use these.
Transformer stock
With the assembly of transformers directly on the ground or on non-insulated running rails, oscillations from the transformer can give off unwelcome noises and vibrations in the surrounding area. For active interference suppression, special transformer stock can be used and can also be re-fitted at any time.
Fixed ball point
Fixed ball points can be included optionally 20mm or 25mm.
Remote-reading indicator thermometer
As a further monitoring system we offer a remote-reading indicator thermometer-monitoring from JUMO:
Data sheet remote-reading indicator thermometer
Data sheet capillary (FL) and temperature probe (TF) for remote-reading indicator thermometer
SGB-SMIT cast resin transformers make minimum demands on the site of installation. This results from the above-mentioned regulations regarding groundwater protection, fire protection, functional integrity in DIN VDE 0101, DIN VDE 0108 and ELT Bau VO (Body of regulations for the building trade).
With SGB-SMIT cast resin transformers, no measures are required for water protection.


If however, the cast resin transformer with a rated voltage of over 1 kV is to be used for facilities accommodating crowds of people according to DIN VDE 0108 and ELT Bau VO, the additional requirements specified in these bodies of regulations apply.
SGB-SMIT cast resin transformers feature the degree of protection IP 00 and are intended for indoor installation. The cast resin surface of the transformer winding is not safe to touch in operation.
Cast resin transformers can be located in the same room as medium- and low voltage switchgear, thus permitting electrical connection over an extremely short distance. As in this case, no additional measures are required for oil collecting pans or fire protection, considerable costs can be saved for transformer cells as far as buildings are concerned. In case of outdoor installation, a housing is mandatory. To this effect, the IP type of enclosure of the housing must be specified by the customer.
Especially extreme installation conditions on site must be taken into account when planning switchgear. Thus, special measures are required e. g. in case of utilization of a cast resin transformer at altitudes above 1,000 m due to the low air density. SGB-SMIT cast resin transformers are specially designed for utilization of cast resin transformers in ships, excavators, seismic areas, wind power plants etc. where increased mechanical strain is involved. SGB-SMIT also takes extreme temperature conditions into account in individual cases such as installation in especially cold or tropical areas, and the transformer design is adapted to local conditions accordingly.
Moreover, SGB-SMIT cast resin transformers feature the decisive advantage that all components are always visible, permitting any mechanical damage to be detected and repaired immediately.
Test | Procedure | Readings | Test criteria |
Measurement of winding resistance | Measurement with direct current (Phase to Phase) on high and low voltage sides | Reading is required to calculate load losses and entry on the test log | None |
Measurement of the voltage transmission ratio and checking the vector group | Using the measuring bridge for transmission ratio measurements | Discrepancies for guaranteed transmission ratio are noted | Guaranteed transmission ratio in accordance with DIN/VDE |
Measurement of impedence (Short circuit voltage uk*) and load losses | Low voltage side is short-circuited, power supply from the high voltage side with 10%-50% of the rated current. Measurement of the current, voltage and load losses of each phase using digital meters. Calculation of losses and uk* with reference to rated current and 75 °C. | Entry of readings into the test log | Guaranteed values in accordance with DIN/VDE |
Measurement of no-load losses and no-load current | Transformer power supply with rated voltage on the low voltage side. Measurement of the current, voltage and no-load losses using digital meters. | Entry of readings into the test log | Guaranteed values in accordance with DIN/VDE |
Insulation test (?applied voltage test“) | Test for insulation winding against earth and winding against winding by using a single-phase test transformer | Test voltages in accordance with DIN/VDE | Passing the test, no flash over |
Alternating current voltage test (?induced voltage test“) | Transformer power supply from the low voltage side | Double rated voltage of 200 Hz, Time: 1 Minute | Passing the test, no flash over |
Measurement of insulation resistance | Metriso Meters | Entry of readings into the test log | Readings above 10.000 M /V. |
Partial discharge test | Three-phase power supply. Run on 180% of the rated voltage: Impulse phase. Run on 130% of the rated voltage: Measurement | Partial discharge gauge less than or equal to 20 pC or customer demand inclusive factor | Readings less than or equal to specification |
Visual inspection |
|
|
|
Test | Procedure | Readings | Test criteria |
Start heating test (no-load measurement) | Measurement of cold resistance using resistance measuring bridge | Recording reading for later use | Comparison with calculated values |
Transformer power supply with the appropriate voltage in accordance with tapping | Measurement of voltage, recording temperatures of iron core and windings by using recorder | Stabilisation of the temperature below specification | |
End heating test (no-load measurement) | Measurement of winding resistance using resistance measuring bridge for 12 minutes every 30 seconds after shutdown | Recording reading for later use | Guaranteed values of temperatures |
Start heating test (Short circuit measurement) | Short circuit of low voltage side, transformer power supply from the high voltage side with the appropriate voltage in accordance with tapping | Measurement of current, recording of temperatures of iron core and windings by using recorder | Stabilisation of the temperature below specification |
End heating test (short circuit measurement) | Measurement of winding resistance using resistance measuring bridge for 12 minutes every 30 seconds after shutdown | Calculation of change in resistance to determine heating | Heating less than specified standards |
Noise measurement | Transformer power supply with rated voltage in the test room. Measurement of noises at 1 m interval with calibrated sound meter. Recording of spectrum. | Entry of readings into the test log | Readings less than specified standards |
Surge voltage test | Transformer shock using surge voltage in accordance with the specified norm | In accordance with the specified norm | Passing the test, recording the shock sequence |
The place at which the cast resin transformer is installed must be adequately ventilated because with each transformer operation, heat loss occurs which must be discharged from the transformer chamber. In so doing it is worth checking whether the possibility is given for natural airing and ventilation. If dimensions of a chamber or enclosure do not guarantee proper cooling, the air rate must then be guaranteed via forced ventilation. Therefore it is immaterial whether the transformers are operated as self-cooling with the cooling method AN or with attached fans for increased capacity. Therefore the ventilation system must be assessed for maximum heat loss arising which is made by iron core no-load losses and the heat energy caused by the coils. In order to achieve natural air circulation, it is important that the additional air entrance port is always arranged below and with a maximum height up to the beginning of the low voltage coil, in order to further the chimney effect and the circulation of the air flow in the channel between the low and high voltage coil. With regard to the planned openings of additional air – intake and extracted air – outtake, it is important that the lower opening under the transformer is preferably all the way around, whereby the upper opening must normally show a cross section around 10 to 15 % higher in order to take the lower density of extracted air into consideration and consequently prevent heating.
The necessary volume for perfect cooling can be calculated as follows:
Q = Pt / (1.15 x ΔO) [m³ / s ]
Effective area of the lower opening can be calculated as follows:
S = 10,752 x (Pt / ((H x ΔO³)0,5))[m²]
Pt: total losses discharged in kW
ΔO: Temperature gradient in °C between additional air and extracted air
Q: Air change in m³
H: Distance in meters between the axis of the transformer and the axis of the upper opening of the booth
S: Effective area in m² of the lower additional air opening (without bars)
Noises occur as a result of magneto-striction of laminations. With distribution transformers it depends on induction and not on strain. Harmonics in voltage, which occur for example as a result of converter operation, heighten the noise. Operational noises of the cast resin transformer permeate on site as airborne sound and mechanical vibration, whereby for each form of sound other measures for noise reduction are adopted.
The airborne noise is heightened in a transformer chamber as a result of reflection on walls and ceilings. This increase depends on the total area of the chamber, the area of the transformer and the noise-absorption coefficient of the construction material used for ceilings and walls. This increase in operational noises as a result of reflection can be greatly reduced by lining the transformer chamber with slag wool. Furthermore the sound pressure level in the chamber is reduced outwards through the walls. This insulation is so much greater the thicker a bricked wall is for example. However what is crucial is that outside the transformer chamber the sound pressure level steadily decreases with distance.
Transformer noises are also carried over the contact areas of the transformer, down to the ground, on the walls and other parts of the transformer chamber, the so-called mechanical vibration. This method of noise transmission can be reduced or prevented through mechanical vibration insulation of the transformer. The intensity of the main outbound operational noises from the transformer can not thereby be reduced although mechanical vibration insulation can contribute greatly towards optimising the insulation of the chamber and can therefore, for example, do without noise absorption lining with slag wool on the walls.
Special transformer supports see to mechanical vibration insulation of SGB transformers. Equally expansion straps can be interposed, for example on site, on the low voltage connection, in order to protect the low voltage connection against mechanical voltages and transmission of mechanical vibration.
If nothing else is demanded from the customer, the cast resin transformers are installed on a chassis roller according to transformer capacity. The noises associated with the transformer operation and vibrations caused are not however always negligible. As a possible step for mechanical decoupling of the transformer from the basis of the site is the use of vibrastops from Kächele or Gummi Technik Wager und Wagner. Transformer supports of both manufacturers do not differ purely visually, however Kächele’s supports are harder and more expensive. In many cases special rubber material from ISOLOC is used, normally IPL 20 material The advantage of this material essentially lies in the fact that absorption material out of sheet material can also be produced for larger transformers. It is then used if the transformer is installed without a chassis.
The previously mentioned transformer supports are restricted in dimensions and maximum permitted loads. For instance the maximum permitted weight for transformer supports from a certain manufacturer is 3000N, which corresponds to a permitted transformer total weight of 30000/10 x 4 = 12000 kg. Cast resin transformers with this weight have a capacity of ca. 5000 kVA.
With installation of the transformer on a rubber support, deflection is to be taken into consideration as the position of the connections can change somewhat as a result. This is critical when connecting transformers to existing railing systems. Subsequently a calculation model for deflection of a rubber support is illustrated:
Total mass of transformer : Number of support points = Strain (F) per support (e.g. 22500 N : 4 = 5500 N)
From the strain F per transformer support in Newtons, the statistical deflection can be calculated in millimeters. This is obtained from the table of the support manufacturers, whereby the mechanical vibration absorption value is then also given in decibles, which depends on the particular transformer support used. The bigger the strain per support, the greater the deflection.
Internal studies in our test room have revealed that the effectiveness in terms of the noise insulation performance is in the region of ca. 1 dB(A), when the cast resin transformer is installed on an appropriate support. It is to be noted however that transmission of vibrations made from the transformer is suppressed better on the whole with a metal rubber deadener in transition, as is the case with noise and vibration deadeners.
When supporting the transformer directly on the ground or on non-insulated running rails, outbound vibrations from the transformer emit unpleasant noises and unwelcome vibrations into the environment.
It is sensible to use transformer supports for active interference suppression and protection of both people and the environment. An upgrading of available installations is possible at any time.
Noise and vibration deadener
Range of application using the example of the noise and vibration deadener EK 290 from Langmatz for transformers with maximum 10000 N ultimate load:
Safeguarding rollers as well as deadening noise and vibration for transformers. The vibration deadeners bring about a deadening of the mechanical vibration transmission of at least 20dB for the main parasitic frequency of 100 Hz with transformers. A deadening is brought about as a result of the constructional separation of the top and bottom section with a special deadening element. The rubber is compressed with the weight of the transformer so that a lateral oscillation deadening and a horizontal deadening arise as a result. Strain of deadener per roller: max. 10000 N
Roller diameter of transformer: 125 – 160 mm
Width of roller: 64 mm
For transformers without rollers, the version with the deadener top and bottom section can be used.
Naturally for other ultimate loads, the corresponding noise and vibration deadener must be used.
Basically it must be pointed out that with increased mechanical strains which occur, for example, in ships, excavators, wind turbines, earthquake areas etc, additional design features are required. This distinguishes SGB Cast Resin Transformers among other things, which have proven themselves worldwide under the most diverse conditions of installation.
Reducing noises from transformers radiating into the circumambient air is becoming more and more important. SGB Cast Resin Transformers are therefore provided both with normal execution in accordance with the German Institute for Standardisation 42 523 and with reduced losses and noises. Apart from the choice of induction and the core material the type of mortise and tenon joint of legs and yokes used by SGB in the "step lap" procedure has a favourable effect on noise properties and on transformer losses.
For specific values for noise for cast resin transformers in an AN operation without enclosure, in practice, the possibilities are:
A – Evaluated sound pressure level LPA in dB
A –Evaluated sound power level LWA in dB and associated measurement surface LS in dB.
Sound power is a measurement for the amount of noise which is produced and generated from a noise recorder. Sound power characterises the noise of the recorder and unlike the sound pressure level does not depend on the measuring position or acoustics in the surrounding area.
The definition of these values and type and how noise measurement is to be carried out is defined in the German Institute for Standardisation 45 635/Part 30. Important terms in this context are:
Reference plane (from the thread measure, which includes the heat radiating surface)
Length of measuring path lm in m
Measurement area S in m²

As with dry-type transformers, but not oil-filled transformers with their scoop-proof vessels, a distance of 0.3m can be measured from the vessel, for safety reasons with cast resin transformers, the measurement is made at a distance of 1 m from the reference plane.
LWA and LPA with LS have the set combination in the German Institute for Standardisation 45 635/Part 30:
LWA = LPA + LS
LS = 10 lg S/S0 dB
S = (h + 1) + lm an S0 = 1 m²
lm = 4 MA + (DWA + 2)π
MA = Dual spacing in m
DWA = Coil outer diameter in m
h = Height of core with clamping bar in m (including castors)

• Protection class IP20 to IP44 available
• Design of cooling from AN (convection-cooled) via AF (fan-cooled) to AFWF (air/water-cooled)
• Low-cost standard enclosures with various equipment options
• Straightforward assembly on site by delivery in preassembled condition
• For indoor installation, we offer IP23 and, for outdoor installation, IP33
• Roof coolers can be provided
• Standard paint RAL 7032 or 7035. Other paint available on request
• For cable connection from below, entry plates and metal supports are provided.
• Entry from above via divided enclosure top.
The enclosures feature air entry and outlet ports to dissipate the transformer‘s power loss for natural or forced air cooling. On the installation site, free supply and discharge of the required cooling air must be ensured.
• 3 sizes
• Type of protection IP 21
• Suitable for floor installation
• With integrated NIEDAX cable fastening
• Delivery in ready-assembled condition or as modular kit for assembly by the customer
• Enclosure components manufactured of hot-galvanized sheet metal

When operated, transformers cause electric and magnetic fields. These electromagnetic fields can attain values to whose assessment the following basis applies:
The Federal Immission Control Act
With the coming into effect of the 26th decree on the 1st January 1997 of the implementation of the Federal Immission Control Act (26. BImSchV), low frequency installations with 50-Hz-fields at the place of influence have to abide by the threshold values of 5 kV/m for electrical field strengths and 100 µT for magnetic induction. Place of influence is the place with the greatest exposure at which not only a sojourn from people is to be expected. The electric field outside the cast resin transformer and its connections are hardly effective outside the transformer booth. The protective enclosure of SGB Cast Resin Transformers acts as a Faraday cage. This also applies as far as possible to ceilings and walls in the transformer booths provided that these do not consist of electrical insulating material. The magnetic transformer scatter fields can give rise to disturbances, which in essence consist of three sources.
Scatter field in no-load
Scatter field from the lead wires
Scatter field from current-carrying coils
The no-load field issues mainly at the top and bottom ends of the coil and from the impact points of the iron core. However the no-load field is clearly smaller than the scatter field from the load current-carrying coils. In the literature for instance, factor 10 is mentioned. Separate measurements have resulted in a magnetic leakage flux density at least four times smaller. Therefore you can disregard the no-load scatter field for calculations.
Like each current-carrying conductor, discharges, like connection cables and busbars set up a scatter field. At every point in the chamber this depends on the vectorial sum of the field strengths caused there by the single current-carrying conductors. With conductor set-ups in which the total currents appear as neutral, like outward and return conduction in the AC circuit or three phases with the three-phase current system, the resultant field is all the more smaller the closer these conductors are together. The load current-carrying coils constitute the largest part of the scatter field, which is overlaid by fields of the low voltage-sided discharges.
These scatter fields were recorded by SGB measurements in order to determine the field and with action a reduction occurs in the fields. For instance, the connected low voltage outgoing circuits were set up point-symmetrically at a 1000VA cast resin transformer, so that the field capacity was able to be minimised as much as possible by means of the cable and at the same time, by using a very simple and assembly friendly aluminium shield box, demonstrating that you could reduce the distance for a lower deviation of the flux density in all directions (x - direction, y - direction, z - direction). Equally recommended for the connection of the transformer is field compensation by means of a double low voltage conduction with point-symmetrical phase sequence, were it to be required.
Transformers are regarded as passive elements in accordance with IEC 60076 with regard to electromagnetic interference emission and interference immunity and a CE marking is not permissible.
In accordance with measurements and calculations, the magnetic field around SGB Cast Resin Transformers as well as SGB oil distribution transformers is significantly below the threshold value, which the 26th decree for the implementation of the Federal Immission Control Act (26. BImSchV) of 16.12.96 stipulated. Capacity transformers are basically exempt from this decree as capacity transformers are to be seen as components of a total system or of an installation. Measures are to be sought to reduce the critical field strengths as well as adherence to threshold values in a system or installation which essentially determine the whole field configuration.
SGB had already started with the calculation and measurement of the electromagnetic field well before this date in order to determine the field around a transformer and to try out measures to reduce the field. Under defined measurement conditions the magnetic field of a cast resin transformer is circa 5 μ , for example, 630 kVA/20 kV-0,4 kV in accordance with separate measurements with a distance of 2 m to the cast resin surface of the coil. With an oil transformer of the same capacity it is less than 2 μ with a distance of 1.7m to the geometric centre. It is evident that the partly magnetic fields by means of currents in the coil in this voltage level (0.4 kV) fall significantly below the permitted 100 μ. Disturbances on the display may arise from 1 μ onwards. Further technical disturbance limits are:
Pacemakers | 50 Hz | 4 - 6 μT |
Hearing aids | 50 Hz | 2 - 20 μT |
ECG | 50 Hz | 0,4 μT |
Pay attention however to the contribution of the current flow in the low voltage connections, e.g. busbars or feed lines. The magnetic field around the feed lines decreases only with the reciprocal value of the square number of the distance, by contrast, around transformers, with the reciprocal value cubic from the distance. It is simply because the current flow in transformers is restricted in a limited space and in feed lines in one dimension expands at will.Therefore the magnetic field around low voltage connections dominates the level of the entire field e.g. in a supply station. A range of measures to optimise the laying of busbars and feed lines, e.g. the batch of outbound connections,have a great effect in reducing induction. The manufacturers of transformers can already create an "interface" for the connection of such optimum laying in the design.
The 26th decree applies to the "fixed installations for the transformation and transmission of electricity". In its area of application it includes "electrical transformation installations including switch bays with a frequency of 50 Hz and high voltage of 1kV or more". As capacity transformers are to be seen as components of a total system, i.e. an appropriate installation, they are exempt from this decree.
The safeguarding of SGB Cast Resin Transformers is with temperature monitoring.
This is ensured with the installation of resistor temperature sensors (PTC) in the low voltage coils and a temperature monitoring instrument. The functionality of the resistors lies in the fact that its resistance rises sharply in a temperature range with increasing temperature and consequently a certain response temperature is reached to which the temperature monitoring instrument immediately responds. If the coil cools around about three Kelvin under response temperature then the temperature monitoring instrument falls back again. Normally two PTC systems are installed which distinguish themselves by 20K separated rated response temperatures (NAT). A PTC System with rotary current transformers is composed of three resistor temperature sensors in series. A temperature sensor for each phase. Thereby the lower rated response temperature is used as a warning and the higher rated response temperature for shutting off the transformer. The first PTC system signals the temperature being exceeded which forms the basis of the normal service life consumption. In this case provisions must be made, so that the strain does not increase further. The operator is therefore warned and should be prompted to find measures to ease the strain. The second PTC system is geared to the maximum temperatire of the declared temperature class. A third system can, for example, assume control of the fans, if transformers are equipped with fans for an increase in capacity of up to 140 % of the rated power. This control of fans happens with PT 100 and a temperature monitoring instrument like, for example, the TS 02. This instrument recognises and signals faults like a short circuit or broken wire in the measurement line, as well as malfunction of the supply voltage. Furthermore the temperature measured is displayed. In addition remote-reading indicator thermometers can be attached too if the customer so wishes. The cost-efficient alternative of temperature monitoring is the use of resistor sensors without displaying the temperature.
For temperature monitoring there is the following choice:
Temperature sensor: PTC, PT 100
Temperature monitoring instruments: TS – 01, TS – 02, TAA – 12
Remote-reading indicator thermometer: for example JUMO
Inrush current:
When activating the transformer large input currents may flow. The inrush current can for example amount to more than ten times the rated current. In order to be able to correctly put safeguards on the entry side of the transformer, it is advantageous to be familiar with the behaviour of the inrush current of the particular transformer. For that reason SGB provides the opportunity to create a diagram for the customer of the inrush current process.
Inrush current process diagram
However the extent to which the transformer should be safeguarded is at the discretion of the operator. In this way surge diverters against high voltages for example can be attached on the high voltage side. The surge diverters that should be used is to be determined by the operator. However it must also be mentioned that safeguarding is dependent upon the nature of the network and this in turn is the responsibility of the operator.
The cast resin transformer must be connected to the earthing (potential equalisation). For this purpose a connection for the earthing at the chassis is available as standard. Customer requests can naturally be taken into consideration, like for example, earthing at the clamping bar.
Connection of earthing and short circuit equipment:
For this purpose fixed ball points of 20mm or 25mm diameter can be attached to the conductor connection straight or angled. There is also the opportunity to attach earthing switches to the high voltage connection side on the transformer or over the course of the high voltage cable connection on the wall.
The earthing and the potential equalisation on the transformer must be connected and checked correctly. Please bear in mind here the torque of the fixing screws and the minimum cross-sections of the potential equalisation conductors. The cross-section of the potential equalisation conductor must be at least half as big as the largest protective earthing conductor cross-section of the installation, but at least 6 mm² copper for mechanical reasons. For potential equalisation conductors, 25 mm² copper is mentioned for non-electrical installations as a satisfactory upper limit. Other than that the whole protective earthing conductor of 50 mm² is to be chosen as a cross-section for the potential equalisation conductor.
Assignment of the minimum cross-sections of protective earthing conductors and neutral conductors to the cross-section of the outer cable in accordance with the Association for Electrical, Electronic & Information Technologies 0100, part 540:
Rated cross-section | |||||
Protective earthing conductor or neutral conductor (PEN)1) | Protective earthing conductor3) moved separately | ||||
Outer cable [mm²] | Insulated high voltage current conductor [mm²] | 0,6/1-kV-cable with 4 conductors [mm²] | protected Cu [mm²] | protected Al [mm²] | unprotected 2) Cu [mm²] |
Up to 0,5 | 0,5 | - | 2,5 | 4 | 4 |
0,75 | 0,75 | - | 2,5 | 4 | 4 |
1 | 1 | - | 2,5 | 4 | 4 |
1,5 | 1,5 | 1,5 | 2,5 | 4 | 4 |
2,5 | 2,5 | 2,5 | 2,5 | 4 | 4 |
4 | 4 | 4 | 4 | 4 | 4 |
6 | 6 | 6 | 6 | 6 | 6 |
10 | 10 | 10 | 10 | 10 | 10 |
16 | 16 | 16 | 16 | 16 | 16 |
25 | 16 | 16 | 16 | 16 | 16 |
35 | 16 | 16 | 16 | 16 | 16 |
50 | 25 | 25 | 25 | 25 | 25 |
70 | 35 | 35 | 35 | 35 | 35 |
95 | 50 | 50 | 50 | 50 | 50 |
120 | 70 | 70 | 50 | 50 | 50 |
150 | 70 | 70 | 50 | 50 | 50 |
185 | 95 | 95 | 50 | 50 | 50 |
240 | - | 120 | 50 | 50 | 50 |
300 | - | 150 | 50 | 50 | 50 |
400 | - | 185 | 50 | 50 | 50 |
PEN-conductor >= 10 mm² Cu or >= 16 mm² Al, in accordance with article 8.2.1 of the Association for Electrical, Electronic & Information Technologies 0100, part 540. Unprotected movement of Al conductors is not permitted. Use bare conductors chiefly from a cross-section of the outer cable of >= 95 mm².
If the capacity of a transformer is not sufficient you can then connect several transformers in parallel. In addition the momentary values of the voltages must be equal and the transformers must change their voltages with strain to the same extent. In distribution networks rotary current transformers for example are operated in parallel in order to supply the low voltage network from the high voltage network. With a voltmeter the low voltage side is checked to see whether the parallel connection was correctly made. If a parallel connection is made, before connection you have to check to see if the high and low voltage cables are connected to all transformers at the same phases and that the switch links are at the same position, so that equal voltage is available at all phases and all instruments and at the output the same stress ratio exists. In addition it is necessary to make a conductive connection between the secondary sides of the transformer with a metal rail in order to be able to compare more easily the voltages of the phases. If there is a neutral conductor it is beneficial to employ a metallic connection. With a voltmeter the value of the potential difference must also be checked. If the measured value is zero this means that all requirements are met for a parallel connection and the high voltage switches can be closed.
To connect rotary current transformers in parallel the following requirements are to be met in accordance with the German Institute for Standardisation and the Association for Electrical, Electronic & Information Technologies 0532:
The high and low voltages must be equal so that the transmission of open circuit voltages is equal as much as possible.
The short circuit voltages of transformers should differ by 10% at most from each other. Thereby you can avoid the transformer with the small short-circuit voltage getting too large a current and being overloaded. If the difference is bigger then inductances can be preceded to increase the short-circuit voltage.
The ratio of rated outputs should be less than 3:1. With larger rated output ratios, equalising currents are able to flow and bring about a phase shift between the output voltages.
The coefficient of vector groups must be equal so that phasing of the output voltages corresponds and no short-circuit occurs.
By way of exception rotary current transformers must be connected in parallel and their coefficient differs by 6, for example Dy5 and Dy11. In addition however the connections must be duly alternated. A check of the phasing is then essential.
If the transformers connected in parallel have equal short-circuit voltage, the entire load is then spread out over the transformers in proportion to the rated outputs. If the short-circuit voltage is different then the transformer is loaded more with the smaller short-circuit voltage. The strain is then greater as it corresponds to the ratio of the rated outputs.