More than 60 years of know-how and experience is reflected in the oil distribution transformers made by SGB-SMIT Group. Our production (in Germany and Malaysia) is based on high-quality production materials, and we place the highest emphasis on first-class workmanship. The result: oil distribution transformers of maximum reliability!


  • Product
  • Selection
  • Technical Information
  • Downloads
  • References
  • Contact / Enquiry
  • Details
  • Quality test

Iron Core

Cold-rolled grain-oriented sheets in "Step-lap" lamination reduce no-load losses and no-load currents as well as noise emission.

Low voltage foil winding

  • axial current distribution adjusts freely
  • reduces shearing forces

 

After winding, the Prepreg is stuck over the conductor sheet to form a compact tube by a tempering process. The mechanical quality of the foil windings is controlled by observing the tube stiffness with the help of special testing equipment and in accordance with the force-distance diagram.

High voltage winding

  • fully and semi-automatic winding machines
  • enamel-insulated winding wire with steady winding pull on carrier cylinder, or directly on the LV winding
  • layer insulation of high-quality cable paper
  • covering bandage made of shrinking foil for compact winding with good short-circuit response and optimum impulse voltage distribution

Assembly of active parts and vacuum drying

  • short-circuit proof assembly with profile steel and
  • support of coils
  • secure fixation of the electrical connections

 

The active part is securely joined to the cover and supported against the bottom of the tank.

 

  • low frequency or solvent vapour drying
  • filling of dried and degassed mineral oil

Tank

  • corrugated tank up to 4 MVA manufactured in-house
  • modern folding facility processes the steel sheet into high-quality corrugated walls
  • after the tank has been robot-welded, it is checked for leakage with control liquid and ultraviolet light.

Cover

The cover is made of doubling-free high-quality steel. It is bolted to the tank, and can also be welded to the tank on request. Besides bushings and lifting lugs the required control and monitoring devices are located on the cover.

Corrosion protection

  • Coating of tank and cover based on hydro-coating material by flooding or dipping method. (Standard RAL 7033)
  • On request the tank can also be manufactured in a hot-dip galvanised design.